Alarm Codes
Room Air Conditioner range:
Indoor unit alarm codes
If timer lamp flashes for 1 second on, 1 second off, this indicates
pre heating on the coil during heating mode and is not an error.
If timer lamp flashes for a number of times and then pauses,
please reference table below. Display will flash as shown in diagram.
LED 301

ارور کولردوتکه هیتاچی
􀃁􀁄􀁖􀁋􀁈􀁖 Range: 􀀶􀁘􀁐􀁐􀁌􀁗􀀒􀀰􀁒􀁑􀁒􀀒􀀰􀁘􀁏􀁗􀁌􀁝􀁒􀁑􀁈􀀃􀁌􀁑􀁇􀁒􀁒􀁕􀀃􀁘􀁑􀁌􀁗
۰۱ Indoor coil is too warm in cooling mode or too cold in heating mode.
Reversing valve or coil thermistor is faulty
۰۲ Forced operation from the outdoor unit.
This is not an error
۰۳ Communication error.
Faulty wiring, indoor or outdoor PCB faulty
۰۴ Outdoor unit fault.
􀀪􀁏􀁌􀁊􀁒􀀃􀁛􀁏􀁌􀀃􀁕􀁜􀁔􀁉􀁌􀁙􀀃􀁖􀁍􀀃􀃅􀁈􀁚􀁏􀁌􀁚􀀃􀁖􀁕􀀃􀁖􀁜􀁛􀁋􀁖􀁖􀁙􀀃􀀷􀀪􀀩􀀃􀀳􀀬􀀫􀀃􀀚􀀗􀀘􀀃􀁛􀁖􀀃􀁊􀁖􀁕􀃄􀁙􀁔􀀃􀁌􀁟􀁈􀁊􀁛􀀃􀁗􀁙􀁖􀁉􀁓􀁌􀁔
۰۶ Float switch activated.
Check pump operation and drain
۰۷
Drain pump forced operation.
Drain test switch in test position, faulty PCB
۰۸ Louvre not opening.
Louvre motor faulty, microswitch faulty, PCB faulty (RAF unit only)
۰۹ Faulty indoor unit thermistor.
Air inlet or coil thermistor not connected, open or short circuited faulty PCB
۱۰ Indoor fan motor over current or abnormal rotation speed.
Faulty motor or PCB
۱۳
Eprom data error.
Faulty PCB
Room Air Conditioner range:
Outdoor unit alarm codes
If indoor unit filter lamp is flashing four times, this indicates an
outdoor unit fault. This is identified by the number of flashes on
LD 301, please see the table right.
If LD 303 is on permanently this is normal operation. If LD 301 is
lit in conjunction with LD 303 this indicates an overload (1)
condition but not an alarm. If LD 302 is lit in conjunction with LD
۳۰۳ this indicates an overload (2) condition but not an alarm and if
LD 301 and LD 302 are lit in conjunction with LD 303, this indicates
an overload (3) condition but not an alarm.
On Multizone systems only, if LD 301 is lit permanently and LD
۳۰۲ is flashing a number of times, this indicates a thermistor fault.
Please refer to the table right for the thermistor that is faulty.
If LD 304 is flashing, the number of flashes indicates a
communication error with the corresponding indoor unit circuit
number. Check cable connections, cable is not short circuited
or open circuit and PCB operation.
LED 301
􀃁􀁄􀁖􀁋􀁈􀁖 Range: 􀀶􀁘􀁐􀁐􀁌􀁗􀀒􀀰􀁒􀁑􀁒􀀒􀀰􀁘􀁏􀁗􀁌􀁝􀁒􀁑􀁈􀀃􀁒􀁘􀁗􀁇􀁒􀁒􀁕􀀃􀁘􀁑􀁌􀁗
۱ Normal, unit powered up
۲ Over current on the compressor
Faulty PCB or locked compressor
۲
with LED302 lit
Over current on the compressor
System power module or PCB failure
۳ Compressor rotation speed is low, abnormal compressor rotor position
Faulty system power module, faulty compressor or PCB
۴ Switching failure on the compressor
Faulty system power module, faulty compressor or PCB
۵ Compressor rotation low with over current detected
High pressure detected, faulty fan motor/circuit or abnormally low voltage
۶
Discharge thermistor temperature rising
Short of refrigerant charge, faulty thermistor, faulty compressor faulty fan motor/circuit or main PCB
۷ 􀀩􀁄􀁘􀁏􀁗􀁜􀀃􀁗􀁋􀁈􀁕􀁐􀁌􀁖􀁗􀁒􀁕􀀃􀀋􀀶􀁘􀁐􀁐􀁌􀁗􀀃􀁄􀁑􀁇􀀃􀀰􀁒􀁑􀁒􀁝􀁒􀁑􀁈􀀃􀁒􀁑􀁏􀁜􀀌
۸
Compressor not accelerating above minimum rotation speed
Short of refrigerant charge or faulty compressor
۹
Communication error
C/D terminals not connected, faulty interconnecting cable PCB failure (Summit and Monozone only)
۱۰ Abnormal voltage
Mains voltage incorrect or faulty reactor
۱۲
Fan motor rotation is abnormal
Faulty fan motor or PCB (check fuse)
۱۳ Eprom error
Main PCB failure
۱۴
Over voltage is detected by system power module
Faulty SPM
LD 302
Flashes
Thermistor that is faulty
۱ Compressor overheat (OH)
۲ Defrost thermistor
۳ Ambient thermistor
۴ Narrow pipe (expansion) thermistor, for circuit 1
۵ Wide pipe (suction) thermistor, for circuit 1
۶ Narrow pipe (expansion) thermistor, for circuit 2
۷ Wide pipe (suction) thermistor, for circuit 2
۸ Narrow pipe (expansion) thermistor, for circuit 3
۹ Wide pipe (suction) thermistor, for circuit 3
Hitachi Price List 2009 | 175
Alarm
code
Category of
failure
Range
Set Free IVX Systems Utopia ES
۰۱ Indoor unit 􀀰􀁕􀁋􀁖􀁖􀁙􀀃􀁜􀁕􀁐􀁛􀀃􀁚􀁈􀁍􀁌􀁛􀁠􀀃􀁋􀁌􀁝􀁐􀁊􀁌􀀃􀁈􀁊􀁛􀁐􀁝􀁈􀁛􀁌􀁋􀀕􀀃􀀭􀁈􀁐􀁓􀁜􀁙􀁌􀀃􀁖􀁍􀀃􀁍􀁈􀁕􀀃􀁔􀁖􀁛􀁖􀁙􀀓􀀃􀃅􀁖􀁈􀁛􀀃􀁚􀁞􀁐􀁛􀁊􀁏􀀃􀁈􀁊􀁛􀁐􀁝􀁈􀁛􀁌􀁋􀀃􀁖􀁙􀀃􀀷􀀪􀀩􀀃􀁍􀁈􀁐􀁓􀁜􀁙􀁌
۰۲ Outdoor unit High pressure trip (41.3bar)
High pressure trip
(۴۱٫۳bar) or phase
reversal
High pressure trip
(۴۱٫۳bar) or phase
reversal
۰۳
Communication
error
Communication error between indoor and outdoor units. Problem with the communication cable,
power to indoor or outdoor unit, dipswitch settings or PCB
۰۴ Communication error between outdoor unit main PCB and Inverter PCB. Problem with cables between
the 2 PCBs, power to the inverter PCB or failure of the PCB
۰۴٫ Communication error between outdoor unit main PCB and fan PCB. Problem with
the cables between the 2 PCBs, power to the fan PCB or failure of the fan PCB
N/A
۰۵
Power supply
Phase failure or reversal N/A
۰۶ Voltage drop to inverter compressor. Problem with mains voltage, capacitors to inverter compressor or
inverter electronics
۰۶٫ Voltage drop to condenser fan inverter. Problem with mains voltage, capacitors to inverter fan or
inverter fan electronics
۰۷ Refrigerant
cycle
Decrease in discharge gas superheat. Excessive refrigerant, indoor expansion valve locked open
(cooling), outdoor expansion valve locked open (heating) or short cycling of air to the indoor unit
۰۸ Increase of compressor temperature. Shortage of refrigerant, blockage in refrigerant cycle, outdoor
expansion valve locked closed (heating), indoor expansion valve locked closed (cooling)
۰۹ Outdoor unit 􀀻􀁏􀁌􀁙􀁔􀁈􀁓􀀃􀁖􀁝􀁌􀁙􀁓􀁖􀁈􀁋􀀃􀁖􀁍􀀃􀃄􀁟􀁌􀁋􀀃􀁚􀁗􀁌􀁌􀁋􀀃􀁍􀁈􀁕􀀃􀁔􀁖􀁛􀁖􀁙􀀕􀀃􀀳􀁖􀁊􀁒􀁌􀁋􀀃􀁍􀁈􀁕 N/A
۱۱
Indoor unit
Inlet air thermistor alarm. Problem with the connection of the thermistor to the PCB, thermistor open or
short circuit or PCB failure
۱۲ Outlet air thermistor alarm. Problem with the connection of the thermistor to the PCB, thermistor open
or short circuit or PCB failure
۱۳ Freeze protection (liquid line) air thermistor alarm. Problem with the connection of the thermistor to the
PCB, thermistor open or short circuit or PCB failure
۱۴ Gas pipe (suction) thermistor alarm. Problem with the connection of the thermistor to the PCB,
thermistor open or short circuit or PCB failure
۱۹ Fan motor alarm. Thermal overload on AC fan motors or over/under current/rotation on DC fan motors
Indoor unit alarm codes
If run lamp flashes for two seconds on, two seconds off, there is a
failure in the communication between indoor unit PCB and controller.
Causes – open or short circuit on wiring, faulty controller or faulty PCB.
If run lamp flashes once per second and displays alarm code please
reference table below. Display will flash as shown in diagram.
Alarm
code
Category of
failure
Range
Set Free IVX Systems Utopia ES
۲۰
Outdoor unit
N/A
Compressor/discharge gas thermistor
alarm. Problem with the connection of the
thermistor to the PCB, thermistor open or
short circuit or PCB failure
۲۱
Discharge pressure transducer alarm. Problem with the
connection of the transducer to the PCB, transducer
open or short circuit or PCB failure
N/A
۲۲ Ambient air thermistor alarm. Problem with the connection of the thermistor to the PCB, thermistor
open or short circuit or PCB failure
۲۳
Compressor/discharge gas thermistor alarm. Problem
with the connection of the thermistor to the PCB,
thermistor open or short circuit or PCB failure
N/A
۲۴
Outdoor unit
Evaporation thermistor alarm. Problem with the connection of the thermistor to the PCB, thermistor
open or short circuit or PCB failure
۲۶
FSVNE only. Suction gas thermistor alarm. Problem with
the connection of the thermistor to the PCB, thermistor
open or short circuit or PCB failure
N/A
۲۹
Suction pressure transducer alarm. Problem with the
connection of the transducer to the PCB, transducer
open or short circuit or PCB failure
N/A
۳۰
System
Incorrect H-LINK wiring. 2 CH boxes are wired in series N/A
۳۱ Incorrect capacity code setting. Indoor units connected
are more than 130% or less than 50%
Indoor and outdoor unit capacity does not
match
۳۲ Loss of other unit communication on the same refrigerant cycle number. Other indoor unit switched off,
Communication wiring error, PCB failure on other unit on the same refrigerant cycle number
۳۵ Duplication of indoor or outdoor unit address on the same H-LINK
۳۶ Indoor/Outdoor unit combination is not compatible
۳۸ Abnormality in protection circuit on the outdoor unit. Incorrect connection to outdoor PCB, failure of PCB
۳۹ Fixed speed compressor over current or under current N/A
۴۱
Pressure
N/A
Outdoor pipe thermistor is over 55oC and
compressor temperature is over 95oC
(cooling mode)
۴۲ N/A
Indoor freeze protection (liquid) thermistor
is over 55oC and compressor temperature
is over 95oC (cooling mode)
۴۳
Pressure ratio falling, protection. Discharge and suction
pressures too close. Check refrigerant charge, failure of
pressure transducer, compressor failure
N/A
۴۴ High suction gas pressure protection N/A
۴۵ High discharge gas pressure protection N/A
۴۷ Low suction pressure protection. Restriction or
shortage of refrigerant
Excessively low evaporating temperature
(-۳۵oC)
System Free
Indoor unit alarm codes
Hitachi Price List 2009 | 177
Alarm
code
Category of
failure
Range
Set Free IVX Systems Utopia ES
۴۸
Inverter
Over current detected. Failure of IPM,
PCB2, locked compressor or abnormally
high discharge pressure
۵۱ Abnormality of inverter current sensor. Failure of sensor
or inverter PCB
Abnormality of inverter current sensor.
Failure of Main PCB, IPM or PCB2
۵۲ Over current on inverter compressor. Failure of
electronics or seized compressor
􀀨􀁉􀁕􀁖􀁙􀁔􀁈􀁓􀁐􀁛􀁠􀀃􀁖􀁍􀀃􀁐􀁕􀁝􀁌􀁙􀁛􀁌􀁙􀀃􀃄􀁕􀀃􀁛􀁏􀁌􀁙􀁔􀁐􀁚􀁛􀁖􀁙
۵۳ IPM protection. Over current, low voltage or overheating
IPM or PCB2 protection. Over current or
overheating
۵۴ 􀀰􀁕􀁝􀁌􀁙􀁛􀁌􀁙􀀃􀃄􀁕􀀃􀁛􀁌􀁔􀁗􀁌􀁙􀁈􀁛􀁜􀁙􀁌􀀃􀁙􀁐􀁚􀁌􀀃􀁗􀁙􀁖􀁛􀁌􀁊􀁛􀁐􀁖􀁕􀀕􀀃􀀶􀁝􀁌􀁙􀀃􀁊􀁜􀁙􀁙􀁌􀁕􀁛􀀃􀁖􀁙
􀁙􀁌􀁚􀁛􀁙􀁐􀁊􀁛􀁌􀁋􀀃􀁈􀁐􀁙􀀃􀃅􀁖􀁞
As Set free, with possibility of outdoor fan
abnormality
۵۵ Controller Short circuit on remote controller wiring, failure of controller or failure of indoor unit PCB
۵۶
Outdoor fan
Abnormality of fan motor position. Transmission failure
on inverter fan motor
N/A
۵۷ Fan controller protection. Abnormal fan speed
Fan motor abnormality. Wiring error between
main and fan PCB or fan motor failure
۵۸ Abnormality of fan controller. Over current or over
􀁛􀁌􀁔􀁗􀁌􀁙􀁈􀁛􀁜􀁙􀁌􀀃􀁖􀁍􀀃􀁊􀁖􀁕􀁛􀁙􀁖􀁓􀁓􀁌􀁙􀀃􀃄􀁕􀁚
N/A
۶۱ Central station Loss of communication of unit, previously detected.
Power to indoor unit, Communication wiring error, PCB failure
۹۶
KPI thermistor
Total heat exchanger room temperature thermistor error. Problem with the connection of the thermistor to
the PCB, thermistor open or short circuit or PCB failure
۹۷ Total heat exchanger outdoor temperature thermistor error. Problem with the connection of the thermistor
to the PCB, thermistor open or short circuit or PCB failure
dd
System Incorrect communication cable wiring. Crossed with remote controller or crossed on CH box
EE System locked out due to outdoor unit alarm reset 3 times in 6 hours
System Free
Indoor unit alarm codes